Farenhyt Fire alarm IFP-50

Farenhyt Fire alarm IFP-50

IFP-50
IFP-50 is an intelligent analog/addressable fire control panel (FACP).
IFP-50 has a single line circuit (SLC) loop for connecting addressable
detectors and modules and has two notification appliance circuits that
can be programmed for notification outputs or auxiliary power. IFP-50
also has a built-in dual line digital fire communicator, Form C trouble
relay, and two programmable Form C relays. The firmware has
powerful features such as detector sensitivity, day/night thresholds,
drift compensation and pre-trouble maintenance alert.
IFP-50 supports a variety of other devices that can be added to the
system such as RA-100 remote annunciator, 5824 serial/parallel printer
interface module (for printing system reports), and 5496 intelligent
power module, and Hochiki or Intelligent Device Protocol (IDP)
devices.
Features
• Built-in support for up to 50 Hochiki devices or 50 IDP detectors and
50 IDP modules
• Uses standard wire—no shielded or twisted pair required
• Built-in digital communicator for remote reporting of system activity
and system programming
• Central station reporting by point or by zone
• Jumpstart® auto-programming
• Supports Class B (Style 4) and Class A (Style 6 or Style 7)
configuration for SLC
• Distributed, intelligent power
• Built-in synchronization for appliances from AMSECO, Gentex®,
Faraday, System Sensor®, and Wheelock®
• Sensor sensitivity settings and day/night sensitivity setting and
automatic drift compensation
• Notification circuits can be configured as 1 Class A (Style Z), 2 Class
B (Style Y), or auxiliary power for resettable, constant, or door holder
power
• Built-in annunciator with a backlit 80-character LCD display
• RS-485 bus provides communication to system accessories
• Built-in RS-232 interface for programming via PC
• Built-in Form C trouble relay rated at 2.5 amps at 24 VDC
• Two built-in Form C programmable relays rated at 2.5 amps at 24
VDC
• SLC device locator can be used to locate a single or multiple
devices on a SLC loop
• System automatically performs detector sensitivity test
• 13 preset notification cadence patterns (including ANSI 3.41) and
four user programmable patterns
• Upload or download programming, event history, or detector status
onsite or from a remote location using a PC and 5650/5651 Silent
Knight Software Suite (SKSS)
• Improvements in SKSS deliver five times faster upload/downloads
• Non volatile event history stores up to 1000 events
• 125 software zones and 125 output groups


(FARENHYT) - Fire Alarm FIRE ALARM